转载请备注(http://www.weijicekong.com/)
宝奥城1.2MWp分布式光伏发电项目
频率电压紧急控制装置专用技术规范
需方:广西英利源盛建设工程有限公司
供方:
日期:2017年5月19日
目 录
目 录·············································································································· 2
1 标准技术参数·································································································· 3
2 项目需求部分·································································································· 3
2.1 货物需求及供货范围一览表·········································································· 3
2.2 必备的备品备件、专用工具和仪器仪表供货表·············································· 4
2.3 技术文件提交单位······················································································· 4
2.4 工程概况····································································································· 5
2.5 使用条件····································································································· 5
2.6 项目单位技术差异表···················································································· 5
2.7 一次、二次及土建接口要求(适用扩建工程)·············································· 6
3 投标人响应部分······························································································ 6
3.1 投标人技术偏差表······················································································· 6
3.2 销售及运行业绩表······················································································· 6
3.3 推荐的备品备件、专用工具和仪器仪表供货表·············································· 6
3.4 最终用户的使用情况证明············································································· 7
3.5 投标人提供的试验检测报告表······································································ 7
3.6 投标人提供的鉴定证书表············································································· 7
1 标准技术参数
投标人应认真逐项填写标准技术参数表(见表1~表3)中投标人保证值,不能空格,也不能以“响应”两字代替,不允许改动招标人要求值。如有差异,请填写投标人技术偏差表(表10)。
表1 频率电压紧急控制装置标准技术参数表
序号 | 参 数 名 称 | 单位 | 标 准 参 数 值 | 投标人保证值 |
1 | *电压测量精度 | V | 误差不大于1%Un | (投标人填写) |
2 | *频率测量精度 | Hz | 0.01Hz | (投标人填写) |
3 | *整组动作时间 | ms | 不大于60ms | (投标人填写) |
4 | 交流电压回路过载能力 | 1.2Un,连续工作;1.4Un,10s | (投标人填写) | |
5 | 交流电压回路功率损耗(每相) | VA | ≤1VA | (投标人填写) |
6 | 装置直流消耗 | W | ≤50W(工作时) ≤80W(动作时) 当招标方提出特殊要求导致装置的接入量超过一定规模时,该指标可适当放宽 | (投标人填写) |
7 | 跳闸触点容量 | 长期允许通过电流不小于5A; 触点断开容量为不小于50W | (投标人填写) | |
8 | 其他触点容量 | 长期允许通过电流不小于2A; 触点断开容量为不小于30W | (投标人填写) |
注 项目单位对标准技术参数表中参数有差异时,可在项目需求部分的项目单位技术差异表中给出,投标人应对该差异表响应。差异表与标准技术参数表中参数不同时,以差异表给出的参数为准。
* 该参数为重要参数。如不能满足要求,将被视为实质性不符合招标文件要求。
表2 打印机标准技术参数表
序号 | 参 数 名 称 | 单位 | 标 准 参 数 值 | 投标人保证值 |
1 | 工作电源 | V | 220 AC | (投标人填写) |
2 | 接口型式 | 与保护装置配套 | (投标人填写) |
注 项目单位对标准技术参数表中参数有差异时,可在项目需求部分的项目单位技术差异表中给出,投标人应对该差异表响应。差异表与标准技术参数表中参数不同时,以差异表给出的参数为准。
表3 保护柜标准技术参数表
序号 | 参 数 名 称 | 单位 | 标 准 参 数 值 | 投标人保证值 |
1 | 尺寸 | mm | 高度2260,宽度800,深度600 | (投标人填写) |
2 | 颜色 | RAL7035,右门轴 | (投标人填写) |
注 项目单位对标准技术参数表中参数有差异时,可在项目需求部分的项目单位技术差异表中给出,投标人应对该差异表响应。差异表与标准技术参数表中参数不同时,以差异表给出的参数为准。
2 项目需求部分
2.1 货物需求及供货范围一览表
表4 货物需求及供货范围一览表
序号 | 名 称 | 单位 | 招标人要求 | 投标人响应 | ||
型式、规格 | 数量 | 型式、规格 | 数量 | |||
1 | 频率电压紧急控制装置 | 台 | 带滑差闭锁 | 3 | RCX-9590P | 3 |
2 | 电能质量在线检测装置 | 台 | 3 | VIP-923D | 3 | |
3 | 柜体及附件 | 面 | 800*650*400 | 3 | 3 | |
4 | 打印机 | 台 | 1 | |||
5 | 其他 | 1 |
表5 可选择的技术参数表
序号 | 名 称 | 参 数 | 投标人响应 | 备 注 |
1 | 装置工作电源 | 220AC | 220AC | |
2 | TA二次额定电流 | 5A | 5A |